The investigation began with an unusual combination of clues. Water was collecting in the cellar and had a noticeable odour, but the area had not recently experienced the kind of heavy rainfall that would normally point towards surface-water or weather-related flooding.
That meant the source had to be established rather than assumed. In an older, multi-tenanted building, several internal and external water routes can potentially contribute to ingress, so the survey needed to narrow the possibilities methodically.
The first stage was a systematic inspection and testing of the property's internal and external hot and cold water pipework. Those checks did not identify a visible leak from the supply systems, allowing the investigation to move towards the wastewater pipework.
Testing then identified a damaged soil pipe at foundation level. When the waste pipe was used, water escaped into the cellar, explaining both the recurring ingress and the odour that had first raised concern.
Tracer dye testing was used to confirm the route between the wastewater system and the cellar. A highly visible dye was introduced into the drainage system so the team could follow its movement and identify where water was escaping.
This provided a direct way to connect use of the wastewater pipework with the ingress at cellar level, helping to isolate the defect without unnecessary opening-up across the building.
Thermal imaging was also used as part of the investigation. By looking for temperature differences associated with hidden moisture, the surveyor could assess the affected structure without relying on destructive exploratory work.
Used alongside the tracer dye test and the wider pipework checks, the thermal survey helped build a clearer picture of the leak location and the moisture associated with it.
Once the damaged soil pipe had been identified, the property owner had a defined defect to act on rather than an unexplained water-ingress problem. A specialist drainage company could then be appointed to repair the pipe.
Sanitisation and drying of the affected cellar were also recommended after the drainage repair, addressing the conditions created by the wastewater ingress before the area was returned to normal use.